CP-9131 the PLC controller

Technical Parameters
General Parameters
System Power |
Power supply: 19.2-28.8Vdc (Nominal:24Vdc)Protection: overcurrent protection, anti-reverse connection protection |
Power Consumption |
50mA@24Vdc |
Internal bus power supply current |
Max:2.5A@5VDC |
Isolation |
System Power to Field Power: Isolation |
Field Power
|
Range:19.2-28.8Vdc(Nominal:24Vdc) |
Field Power Current
|
Max.DC 8A |
IO Modules Supported
|
32 pcs |
Wiring
|
Max.1.5mm²(AWG 16) |
Mounting Type
|
35mm DIN-Rail |
Size
|
115*51.5*75mm |
Weight
|
130g |
Environment Specification
Operational
Temperature
|
-40~85℃ |
Operational
Humidity
|
5%~95% RH(No Condensation) |
Protection Class |
IP20 |
Interface Parameter
Note: M represents the valid parameters of master mode, S represents the valid parameters of slave mode, and F represents the valid parameters of free transparent transmission mode
Programming Specification |
|
Programming Software |
CIACON |
Program Storage |
127KBytes |
Data Storage Unit |
52KByte |
Run-Time System |
Multiple PLC Task |
Programming Language |
IEC 61131-3 (LD, IL, ST, FBD, SFC) |
RTC |
Supported |
Max. Task |
3 |
Max. Cyclic Task |
3 |
Max. State Task |
3 |
Scanning Time |
1ms |
Interface Parameters |
|
Max. Extension Module |
32 |
Max. Input Size |
512 Word(1024Byte) |
Max. Output Size |
512 Word(1024Byte) |
Max. Nodes Number |
Restricted by the Ethernet specification |
Baud Rate |
10/100Mbps, Self-adaptive, full duplex |
Network Protocol |
Modbus TCP、Modbus RTU |
serial Port Configuration(RS485) |
Modbus RTU,Baud Rate:2400~115200bps |
LED Indicator |
6 pcs of LED Indicator
PWR
STAT
RUN
ERR
IRN
IER
|
CP-9131 Modbus Connection Parameters