Leave Your Message
Products Categories
Featured Products

CT-124H Digital Input Module 32DI 24VDC Sink or Source Type

CT-124H: 32 channels digital input, sink or source, 34Pin male connector, 24Vdc, counting function supported (counting frequency up to 200Hz)

◆ the module supports 32 channels digital input, it supports sink input and the input high level is valid as it could support PNP sensor; it also supports source input and the input low level is valid as it could support NPN sensor.

◆ the module could collect the digital output signal of field equipment (dry contact or active output).

◆ the module could be connected to 2-wire or 3-wire digital sensor.

◆ the internal bus of the module and field input are isolated by optocoupler.

◆ the module supports input signal holding function, holding time can be set.

◆ after adding counting submodule in ODOT configured software, the counting function is effective.

◆ each input channel of the module supports 32-bit counter with counting frequency <200Hz.

◆ the module could be set the digital signal input filter time and counter byte transmission sequence.

◆ each channel of the module could be set the counting mode and counting direction independently

    Product Details

    ct-124h393

    Technical Parameters

    General parameters

    Power Max.60mA@5.0Vdc
    Isolation I/O to internal bus: opto-couple isolation (3KVrms)
    Field Power Nominal:24Vdc, Range: 19.2-28.8Vdc
    Wiring 34P male connector 2.54mm Pin header
    Mounting Type 35mmDIN-Rail
    Size 115*14*75mm
    Weight 65g

    Environment Specification

    Operational
    Temperature
    -35~70℃
    Operational
    Humidity
    5%~95% RH(No Condensation)
    Protection Class IP20

    Input parameters

    Channel Number 32 channels input
    LED Indicator 32 channels input LED indicator
    Turn-on voltage High input: Min.10Vdc to Max.28Vdc (Common Terminal:0Vdc)
    Low input: Min.0Vdc to Max.14Vdc (Common Terminal:24Vdc)
    Turn-off voltage High input:Max.5Vdc (Common Terminal:0Vdc)
    Low input: Min.19Vdc (Common Terminal:24Vdc)
    Turn-on current Max.5mA/channel@28V
    Input impedance >7.5kΩ
    Input delay OFF to ON: Max.3ms
    ON to OFF: Max.2ms
    Filter time Default 10ms
    Sample frequency 500Hz
    Counter frequency <200Hz

     

     