- IO Modules
- Protocol Converter
- PLC
- Industrial Switch
CT-222F Automation Control Digital Output 16 Channel 24VDC Source Type
-
1. Module Type2. State indicator3. N/A4. Wiring Terminal and identification5. Internal Bus6. Field Power7. Buckle8. Grounding Resilient Sheet9. Fixed Wiring Harness
| General Parameters | |
Power |
Max.83mA@5.0VDC |
Isolation |
I/O to internal bus: opto-couple isolation (3KVrms) |
Field Power |
Nominal:24VDC, Range: 19.2~28.8VDC |
Wiring |
Max.: AWG 18 Min.: AWG 24 |
Installation |
35mm DIN-Rail |
Size |
115*14*75mm |
Weight |
65g |
Environment Specification | |
Operating Temperature of Vertical Installation |
-35℃~70℃ |
Operating Temperature of Horizontal Installation |
-35℃~60℃ |
Relative Humidity |
5~ 95%RH (No Condensation) |
Storage Temperature |
-40℃~85℃ |
Storage Humidity |
5~ 95%RH (No Condensation) |
Manufacturing Test Temperature |
-40℃~75℃ |
Ingress Protection Rating |
IP20 |
Vibration Resistance |
Comply with IEC 61131-2 and EC 60068-2-6 |
Impact resistance |
Comply with IEC 61131-2 and IEC 60068-2-27 |
EMC Performance |
Comply with IEC 61131-2 and IEC 61000-4 |
Output Parameters | |
Channel Number |
16 channel source type output |
LED Indicator |
16 channel output LED indicator |
Rated Current |
Typical value: 500mA |
Leakage Current |
Max:10uA |
Output Impedance |
<200mΩ |
Output Delay |
OFF to ON: Max.100us ON to OFF: Max.150us |
Protection |
Overtemperature shutdown: typical value is 135℃ Overcurrent protection: typical value 1.1A Short circuit protection support |
Load type |
GENERAL USE LOADS, PILOT DUTY LOADS |