CT-5321 Modbus Serial Port Module

CT-5321 Modbus Serial Port Module

1 Module Description

The Modbus serial port module supports 1 channel RS485/RS232 /RS422(optional), supports Modbus RTU/ASCII protocol, and supports master, slave and free transparent transmission mode.

The serial Module CT-5321 could be applied with the adapter modules, so it could convert Modbus into other protocols such as Modbus TCP, Profinet, EtherCAT, EtherNet/IP, etc. When the module is used, serial port parameters and Modbus instructions should be configured in IO Config software.

Devices with RS485/RS232/RS422 interface, which support modbus-RTU/ASCII, could be applied with CT-5321 to realize interconnection with upper PLC or upper computers. CT-5321 could be applied with devices such as: PLC, DCS, remote IO, VFD, motor start protection device, intelligent high and low voltage electrical apparatus, power measurement device, intelligent field measurement equipment and instruments, etc.

    Technical Parameters
    CT-5321-Modbus-Serial-Port-Modulefsx
    Technical Parameters
    General parameters
    Power Max.500mA@5.0Vdc
    Isolation I/O to internal bus: opto-couple isolation (3KVrms)
    Field Power Nominal:24Vdc, Range:19.2-28.8Vdc
    Wiring I/O Wiring: Max.1.5mm²(AWG 16)
    Mounting Type 35mmDIN-Rail
    Size 115*14*75mm
    Weight 65g
    Environment Specification
    Operational Temperature -35~70℃
    Operational Humidity 5%~95% RH(No Condensation)
    Protection Class IP20
    Serial Port Parameters
    M/S/F:Channel
    Number
    1Channel
    M/S/F:Interface RS485/RS232/RS422
    M/S:Protocol Modbus RTU/ASCII
    M/S/F:Working
    Mode
    Modbus Master, Slave, Transparent Transmission
    M/S/F:Baud Rate 300bps-500Kbps
    M/S/F:Data Bit Bit 7, Bit 8
    M/S/F:Parity
    Checking
    None, Odd, Even
    M/S/F:Stop Bit Bit1, Bit2
    M/S/F:
    Character Interval
    1.5t-200t
    F: Byte Order
    Conversion
    Prohibit, Enable
    M/F:Response
    Timeout
    Customized, default: 1000
    M/F: Polling
    Timeout
    Customized, default: 100
    M: Read Data
    Processing Mode
    Hold the last input value, clear the input value
    M: Data
    Output Mode
    Polling, event triggering (data changes)
    M: Module
    Control Enable
    Prohibit, Enable
    M: Module
    Control Mode
    Level trigger (continuously valid), rising edge trigger (single
    valid)
    M: Power on
    Event Output
    Prohibit, Enable
    S:Slave ID Customized, default: 1
    S:Response
    Time
    Customized, default: 50

    Note: M represents the valid parameters of master mode, S represents the valid parameters of slave mode, and F represents the valid parameters of free transparent transmission mode