Leave Your Message
Products Categories
Featured Products

DN-8033 High-speed EtherCAT Network Adapter

The DN-8033 EtherCAT I/O module supports standard EtherCAT protocol access. The adapter supports a Max. input of 682 bytes and a Max. output of 597 bytes. It supports 
32 pcs of extended IO modules.

    • Min. Cycle Time
      0.6 ms
    • Expansion
      32 Modules
    • Wirring Diameter
      Min.0.2mm²(AWG24) Max.1.5mm²(AWG16)
    • Service
      ODM&OEM

    PRODUCT DESCRIPTION

    ODOT DN-8033 EtherCAT Adapter
    EtherCAT, the Industrial Ethernet technology invented by Beckhoff, makes machines and systems faster, simpler and more cost-effective. EtherCAT is regarded as the "Ethernet fieldbus" because it combines the advantages of Ethernet with the simplicity of classic fieldbus systems and avoids the complexity of IT technologies.

    ODOT DN-8033 EtherCAT I/O system
    The ODOT DN-8033 is a user-centric EtherCAT network adapter designed to connect ODOT C-Series remote I/O modules to standard EtherCAT networks.

    Key Technical Features

    • 793a0eed-e7fd-4cec-aed4-8a7c7fe1935d

      Removeable terminals _ Easier Installation

      (1) Staggered spring-loaded guided terminals
      (2) Removeable terminals for easy module maintenance and replacement

    • abe40f07-4608-4e6f-a439-8cdac43443d5

      Redundant Backplane _ Enhanced Reliability

      (1) Backplane bus supports redundancy
      (2) Supports up to 32 I/O modules
      (3) Full load refresh cycle of 0.6 ms

    • 0841450c-88dd-4af9-ae75-61adb10a1291

      Superior EMC Performance

      EMC performance far exceeds IEC 61000-4 standard

    Technical Specifications

    General Parameters

    Module Consumption

    112mA@24VDC

    System Power

    19.2~28.8VDC (Nominal: 24VDC)     Anti-inversion protection: support

    Internal Bus Supply Current

    Max.2A@5VDC

    Filed Power

    19.2~28.8VDC (Nominal: 24VDC)

    Field Power Current

    Max. DC 8A

    Wirring Diameter

    Min.0.2mm²(AWG24)          Max.1.5mm²(AWG16)

    Terminal Pluggable

    Support

    The Maximum Number of Expansion Modules

    32

    Diagnosis Function

    Communication diagnostics, extended module status diagnostics

    Backplane Bus

    Double bus redundancy

    Installation

    35mm DIN-Rail

    Dimension

    119*83*80mm

    Product Certification

    CE Certification

    Communication Parameters

    Protocol

    EtherCAT slave

    Protocol

    2*RJ45

    Line Length

    Maximum 100m (segment length) between 2 sites

    Transmission Speed

    100 Mbps

    Maximum Number of Input/Output Bytes

    Input: 1024 Bytes               Output: 1024 Bytes

    Site Alias Settings

    Dial switch or software configuration

    Environment parameters

    Horizontal Installation Operating Temperature

    -35℃~60℃

    Vertical Installation Operating Temperature

    -35℃~50℃

    Storage Temperature

    -40℃~85℃

    Environment Humidity

    5%~95%RH (No condensation)

    Installation Altitude

    <2000m

    Pollution Degree

    Protection Grade

    IP20

    Mechanical Properties

    Comply with IEC60068-2-6, IEC6008-2-27

    Insulation Withstand

    Comply with IEC61131-2

    EMC Performance

    Comply with IEC61131-2, IEC61000-4

    ESD: Contact discharge±6kV, Air discharge±8kV, Performance

    level A; SURGE: Common mode ±2kV, Differential mode±1kV,Performance level A; EFT: ±2kV, Performance level A)

    S FAQ

    PRODUCTS FAQ

    needs
    9623b2b9-15e5-4a0a-a03f-9a50f54e0200
    Q: What EtherCAT features does the DN-8033 support, and what are its maximum I/O and process data capacities?

    A:The DN-8033 fully complies with the standard EtherCAT protocol and supports 100 Mbit/s Ethernet communication. It can expand up to 32 I/O modules with up to 1,024 bytes of input and 1,024 bytes of output process data. SDO master configuration via EtherCAT master software enables flexible system integration.

    fca08b09-f435-4767-b405-388d9ef8ffbc
    Q:How does the DN-8033 ensure stability and noise immunity during high-speed communication?

    A:With a high-speed redundant backplane bus achieving a full-load refresh cycle of just 0.6 ms, the module provides complete electrical isolation between the internal bus, system power, and field power—effectively blocking field noise from disrupting communications. It also includes built-in communication diagnostics and extended module status monitoring.

    Typical Applications


    Ideal for industries requiring high-speed, cost-effective remote I/O:
    028b1436-959e-44ff-b889-9843d451c8c4

    Why Choose ODOT?

    We understand the challenges the automation industry faces today. The DN-8033 is more than just a hardware component; it's a solution designed to optimize your business efficiency.


    minimized
    Fast & Reliable Delivery
    If you are facing: Global supply chain disruptions causing long lead times (6-12 months) for critical automation parts.

    Our Solution: We maintain a robust supply chain and ample stock levels. ODOT guarantees rapid delivery (Most products can be shipped within 1-3 working days,typically shipping within 1-2 weeks for standard orders), ensuring your project stays on schedule and machine downtime is minimized.
    24/7 Global Technical Support
    If you are facing: Lack of timely support during commissioning, leading to project delays.

    Our Solution: We provide 24-hour technical support. Our team of dedicated application engineers is available around the clock to assist with GSDML file configuration, PLC integration (Siemens S7-1200/1500, etc.), and troubleshooting, ensuring a smooth setup process regardless of your time zone.
    Certifications & Quality Assurance:
    ODOT products comply with international industrial standards, including CE,UL, RoHS, CL and CCS certifications, having undergone rigorous quality control to ensure long-term reliable operation in industrial environments.
    environments
    ODOT In Hannover Messe
    Germany
    Professional Team
    Team

    Leave Your Message

    New Products Recommendation