- IO Modules
- Protocol Converter
- PLC
- Industrial Switch
DT-1314 Digital Input Module 4DI
Module Features
Technical Parameters
|
General Parameters |
|
|
Current Consumption |
45mA@5VDC |
|
Field Power |
19.2~28.8VDC (Nominal: 24VDC) |
|
Wirring Diameter |
Min.0.2mm²(AWG24) Max.1.5mm²(AWG16) |
|
Terminal Pluggable |
Support |
|
Backplane Bus |
Double bus redundancy |
|
Installation |
35mm DIN-Rail |
|
Dimension |
119*14*80mm |
|
Product Certification |
CE Certification |
|
Input Parameters |
|
|
Number of Channels |
4 Channels input |
|
Indicator |
4 Channels indicators |
|
Input Characteristics |
IEC 61131, Type 1@110VAC/ Type 3@220VAC |
|
Voltage Frequency |
AC(47 Hz to 63 Hz) |
|
Rated Value |
100~240VAC |
|
Signal “0 ” |
0~40VAC |
|
Signal “ 1 ” |
74~264VAC |
|
OVC |
Ⅱ |
|
Input Delay |
OFF to ON: Max.4ms ON to OFF: Max. 10ms |
|
Channel Isolation |
Isolation |
|
Environment Parameters |
|
|
Horizontal Installation Operating Temperature |
-35℃~60℃ |
|
Vertical Installation Operating Temperature |
-35℃~50℃ |
|
Storage Temperature |
-40℃~85℃ |
|
Environment Humidity |
5%~95%RH (No condensation) |
|
Installation Altitude |
<2000m |
|
Pollution Degree |
Ⅱ |
|
Protection Grade |
IP20 |
|
Mechanical Properties |
Comply with IEC60068-2-6, IEC6008-2-27 |
|
Insulation Withstand |
Comply with IEC61131-2 |
|
EMC Performance |
Comply with IEC61131-2, IEC61000-4 (ESD: Contact discharge ±8kV, Air discharge ± 15kV, Performance level B SURGE: Common mode±3kV, Performance level B EFT: ±2kV, Performance level A) |

Automotive Industry