DT-3714 Analog RTD Input Module 4CH RTD-PT100

4 Channels RTD input module RTD-PT100

    Module Features

    ◼ The module supports channel disable, support the PT-100 2-wire or 3-wire.
    ◼ The filter level of module is adjustable.
    ◼ The module supports fault detection (disconnection, short circuit, overflow, underflow, terminal state).
    ◼ Module high speed redundant backplane bus with pluggable terminal blocks.

    Technical Parameters

    General Parameters

    Current Consumption

    39mA@5VDC

    Wirring Diameter

    Min.0.2mm²(AWG24)

    Max.1.5mm²(AWG16)

    Terminal Pluggable

    Support

    Backplane Bus

    Double bus redundancy

    Installation

    35mm DIN-Rail

    Dimension

    119*14*80mm

    Product Certification

    CE Certification

    Input Parameters

    Channel Number

    4 Channels RTD-PT100 input

    Input Range

    2-wire or 3-wire

    Measurement Range

    -200~850℃

    Resolution

    16 Bit (include the symbol bit)

    Transition Time

    360ms/4 channels (filter level is 0)

    Linearity Error

    ≤±0.01%

    Measurement Error

    ≤±0.6 (@25), ≤±1.5 (@-35~60)

    Repeatability

    ≤±0.005% (@25)

     

    Module Diagnosis

    ADC fault: support

    Break/short circuit detection: support

    ADC conversion abnormal: support

    Overflow /Underflow: support

    Unit of Measurement

    Configurable, °C / °F / K

    Environment Parameters

    Horizontal Installation Operating Temperature

    -35~60

    Vertical Installation Operating Temperature

    -35~50

    Storage Temperature

    -40~85

    Environment Humidity

    5%~95%RH (No condensation)

    Installation Altitude

    <2000m

    Pollution Degree

    Protection Grade

    IP20

    Mechanical Properties

    Comply with IEC60068-2-6, IEC6008-2-27

    Insulation Withstand

    Comply with IEC61131-2

     

    EMC Performance

    Comply with IEC61131-2, IEC61000-4

    (ESD: Contact discharge ±6kV, Performance level A; Air

    discharge±8kV, Performance level A

    SURGE: Common mode ±2kV, Performance level A

    EFT: ±2kV, Performance level A)