DT-3804 Analog Thermocouple Input Module 4AI
Module Features
Technical Parameters
|
General Parameters |
|
|
Module Consumption |
36mA@5VDC |
|
Wirring Diameter |
Min.0.2mm²(AWG24) Max.1.5mm²(AWG16) |
|
Terminal Pluggable |
Support |
|
Backplane Bus |
Double bus redundancy |
|
Installation |
35mm DIN-Rail |
|
Dimension |
119*14*80mm |
|
Product Certification |
CE Certification |
|
Input Parameters |
|
|
Channel Number |
4 Channels |
|
Sensor Type |
J / K/ E / T / S / R / B / N type thermocouple |
|
Resolution |
16 Bit (include the symbol bit) |
|
Temperature Compensation |
Fixed reference temperature/external reference junction |
|
Conversation Time |
500ms/4 channels (filter level is 0) |
|
Linearity Error |
≤±0.01% |
|
Temperature Error |
≤±0.005%/℃ |
|
Temperature Error |
≤±0.03% (@25℃) |
|
Measurement Error |
See schedule 1 below for detailed parameters |
|
Module Diagnosis |
Disconnection detection: support Overflow/underflow: support |
|
Temperature Unit |
Configurable, ℃ / ℉ / K |
|
Environment Parameters |
|
|
Horizontal Installation Operating Temperature |
-35℃~60℃ |
|
Vertical Installation Operating Temperature |
-35℃~50℃ |
|
Storage Temperature |
-40℃~85℃ |
|
Environment Humidity |
5%~95%RH (No condensation) |
|
Installation Altitude |
<2000m |
|
Pollution Degree |
Ⅱ |
|
Protection Grade |
IP20 |
|
Mechanical Properties |
Comply with IEC60068-2-6, IEC6008-2-27 |
|
Insulation Withstand |
Comply with IEC61131-2 |
|
EMC Performance |
Comply with IEC61131-2, IEC61000-4 (ESD: Contact discharge ±6kV, Performance level A; Air discharge±8kV, Performance level A SURGE: Common mode ±2kV, Performance level A EFT: ±2kV, Performance level A) |
|
Type of Sensor |
Measurement Range (Unit: ℃) |
Measurement Accuracy (25℃) |
Measurement Accuracy (-35℃~60℃) |
|
B |
600≤T≤1820 |
≤0.2% |
≤0.4% |
|
E |
-200≤T≤1000 |
≤0.2% |
≤0.4% |
|
-250≤T<-200 |
≤0.5% |
≤0.6% |
|
|
N |
-200≤T≤1300 |
≤0.2% |
≤0.4% |
|
-250≤T<-200 |
≤0.5% |
≤0.6% |
|
J |
T>-210 |
≤0.2% |
≤0.4% |
|
K |
-200≤T≤1370 |
≤0.2% |
≤0.4% |
|
-250≤T<-200 |
≤0.5% |
≤0.6% |
|
|
R |
0≤T≤1760 |
≤0.2% |
≤0.4% |
|
S |
0≤T≤1760 |
≤0.2% |
≤0.4% |
|
T |
-200≤T≤400 |
≤0.3% |
≤0.5% |
|
-250≤T<-200 |
≤0.6% |
≤0.7% |

Automotive Industry