- IO Modules
- Protocol Converter
- PLC
- Industrial Switch
DT-4164 Analog Voltage Output Module 4AO
Module Features
Technical Parameters
|
General Parameters |
|
|
Current Consumption |
169mA@5VDC |
|
Field Power |
19.2~28.8VDC (Nominal: 24VDC) |
|
Wirring Diameter |
Min.0.2mm²(AWG24) Max.1.5mm²(AWG16) |
|
Terminal Pluggable |
Support |
|
Backplane Bus |
Double bus redundancy |
|
Installation |
35mm DIN-Rail |
|
Dimension |
119*14*80mm |
|
Product Certification |
CE Certification |
|
Input Parameters |
|
|
Channel Number |
8 channels voltage output |
|
Resolution |
16 bits |
|
Output Range |
0~5V/0~10V/ -5V~5V/ -10V~10V |
|
Transition Time |
1.5ms/8 channels |
|
Short-circuit Current |
15mA |
|
Linearity Error |
≤±0.03% |
|
Temperature Error |
≤±0.005%/℃ |
|
Repeatability |
≤±0.05% |
|
Measurement Error |
±0.2% (@25℃), ±0.4% (@-35℃~60℃) |
|
Diagnosis Function |
DAC overheating fault: Support |
|
Environment parameters |
|
|
Horizontal Installation Operating Temperature |
-35℃~60℃ |
|
Vertical Installation Operating Temperature |
-35℃~50℃ |
|
Storage Temperature |
-40℃~85℃ |
|
Environment Humidity |
5%~95%RH (No condensation) |
|
Installation Altitude |
<2000m |
|
Pollution Degree |
Ⅱ |
|
Protection Grade |
IP20 |
|
Mechanical Properties |
Comply with IEC60068-2-6, IEC6008-2-27 |
|
Insulation Withstand |
Comply with IEC61131-2 |
|
EMC Performance |
Comply with IEC61131-2, IEC61000-4 (ESD: Contact discharge ±6kV, Performance level A; Air discharge±8kV, Performance level A SURGE: Common mode ±2kV, Performance level A EFT: ±2kV, Performance level A) |