MG-CANEX CANopen to Modbus TCP Protocol Converter Gateway
Product Details
◆ The gateway comes with its own configuration software, and the parameter configuration information is downloaded to the gateway through the network port. The gateway automatically saves the latest configuration information. There is no need to load configuration after the gateway is powered off and on.
◆ Gateway is the master of CANopen on CANopen network, and can connect to the equipment of CANopen slave
◆ The gateway is Modbus Server on Modbus TCP network and supports up to 5 TCP clients access. Double Ethernet port, with switch function, support cascade.
◆ 2KV network port isolation protection, 10M/100Mbps rate adaptive, automatic MDI/MDIX reversal.
◆ It supports address mapping mode, and realize the rapid response to TCP client request.
◆ Modbus TCP supports function code: 0 x01, 0 x02, 0 x03, 0 x04, 0 x05, 0 x06, 0 x0F, 0 x10.
◆ 6KB large data buffer, more data transfer volume.
◆ CAN interface supports CANopen working mode.
◆ CAN interface Baud rate: 10K~1Mbps.
◆ CANopen protocol conforms to DS301 V4.02 and supports NMT master, PDO, SDO and Heartbeat.
◆ It supports one-key reset function to restore factory Settings.
◆ 35mm DIN-rail installation.
◆ EMC meets EN 55022:2010 & EN55024:2010 international standards.
Technical Parameters
Please use this product within the parameters of this product to obtain better performance.
| Environmental parameters | |
| Working temperature | -40~85℃/-20~70℃ optional |
| Storage temperature | -45~125℃ |
| Working humidity | 5%~95% ( No condensation ) |
| The power supply parameters | |
| Number of power ports | 1way |
| Input voltage range | 19.2~28.8VDC, 3KV isolation voltage |
| Power consumption | Max.110mA@24V |
| Ethernet parameters | |
| Modbus TCP Function code | 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F, 0x10 |
| Number of Ethernet ports | 2PCs of RJ45, 10M, 100M adaptive rate with switch function |
| Network protocol | ETHERNET, ARP, IP, TCP, ICMP |
| Number of TCP connections | The five largest |
| Modbus data store | |
| 0xxxx area(coil) | 8192 Bit |
| 1xxxx area(Discrete input ) | 8192 Bit |
| 3xxxx area(Input register ) | 2048 Word |
| 4xxxx area(Hold register ) | 2048 Word |
| CANopen parameters | |
| CAN baud rate | 10K~1Mbps |
| CAN protocol | CANopen |
| Number of slave supported | 16 stations |
| PDO functions | Support TPDO, RPDO data transmission |
| SDO functions | Fast SDO transfers of up to 4 bytes are supported |
| Error control | Support the Heartbeat |