Leave Your Message

Example of communication for the CN-8031 module

2025-06-06

1 Topology

1

2 Example of communication for Modbus Poll software with module

  1. 1.In IO Config software, it can view the default parameters of CN-8031 module, Modbus Tcp parameters: IP address (192.168.0.100).

2

  1. 2. Use IO Config software to monitor CN-8031 and the address table of the attached Io Module online.
    Note: After the IO module is fixed in order, its Modbus address is fixed.
    For example, the address table of the I/O modules is as follows:
    The address area corresponding to CT-121F is:10000~10015,
    The address area corresponding to CT-222F is:00000~00015,
    The address area corresponding to CT-3134 is:30000~30003,
    The address area corresponding to CT-4234 is:40000~40003.

3

3.Open the Modbus Poll software, click connection, select the MODBUS TCP, and the IP Address is 192.168.0.100, 502, click OK. Click Setup-Read/Write Define, select the function code, start address, and data length to monitor the value of the I/O module.

45

Power the DI0 of the CT-121F to 24V, assign 1 to the DO8 of the CT-222F, assign the AO0 channel of the CT-4154 to 3000, and connect the AI0 channel of the CT-3134 to the AO1 channel of the CT-4154 to 2000, and connect the AI1 channel of the CT-3134 at the same time.

6

  1. 4. Online diagnosis
    On the interface of the Modbus poll software, use the Modbus 04 function code to capture the status input of the module as shown in the following figure:

7

It can see from the screenshot:
There is no DIP on the lower left side of the hardware, and the DIP value is 0 by default.
Module IP address 192.168.0.100.
The size of the input and output data of the module.
There is a value for the configuration port, that is, the online connection of the configuration software is configured.
The MODBUS TCP client has 1 connection here.

3 Example of communication between Siemens S7-1200 (TIA V16) and module

This application uses Siemens TIAV16 software, and Siemens PLC S7-1214C DC/DC/DC is used as a Modbus TCP client to connect to CN-8031 Modbus TCP adapter for test and demonstration.
Note: After the IO module is fixed in order, its Modbus address is fixed.
For example, the address table of the I/O modules is as follows:
The address area corresponding to CT-121F is:10000~10015,
The address area corresponding to CT-222F is:00000~00015,
The address area corresponding to CT-3168 is:30000~30007,
The address area corresponding to CT-4154 is:40000~40003,
1. Open the TIA software and create a new project 1200_MB_CLIENT.Click Add New Device - Select 6ES7 214-1AG4040-0XB0 - Click OK.

8

2. Select the PLC network port in the pop-up interface, set the Ethernet address parameters, add a new subnet PN/IE_1, and set the IP address 192.168.1.10 in the project.

9

3. Add a new block in the block drop-down menu, and add data blocks DB1 and DB2. DB1 is used to store read and write data, and DB2 is used to establish a connection between S7-1200 and CN-8031 (IP address of CN-8031: 192.168.1.100, configure software configuration).

10

11

Note: right-click DB1 and DB2 to select the properties, remove the √ before optimized block access.

12

4. In the program block drop-down menu, double-click Mian [OB1], find the http: // www.odotautomation.com 38 / 159 TEL: +86-0816-2538289 command on the right MB_CLIENT drag it to program section 1. Modify the parameters as shown in the figure.

13

  1. 5. After the setting is completed, save, compile and download.

14

6. Online monitoring of DB1 value. The first input channel of the CT-121F, DI0, is connected to a 24V power supply through an external wiring and the corresponding value can be monitored on DB1.

    15

    The second input channel of the CT-121F, DI1, is connected to a 24V power supply through an external wiring, and the corresponding value can be monitored on DB1.

    16