- IO Modules
- Protocol Converter
- PLC
- Industrial Switch
ODOT CN-8011 Modbus-RTU IO Module Bus Adapter Remote Control
-
Min. Cycle Time2ms
-
Expansion32 Modules
-
Warranty3 Years
-
ServiceODM&OEM
PRODUCT DESCRIPTION
Key Technical Features
-
High-Speed Communication
Spring terminal design for convenient and fast wiring.
-
Innovative Design
Industrial light guided terminal.
-
Space Saving
The product carries ultra-thin design for space saving.
-
High Speed
12M CANBUS backplane carrying 32 modules of a refreshing period at 2ms.
Technical Specifications
|
Hardware Parameter |
|
|
System Power |
Nominal:24VDC, Range: 19.2~28.8VDC |
|
Power Consumption |
30mA@24VDC |
|
Internal Bus Supply Current |
Max:2.5A@5VDC |
|
Isolation |
System Power to Field Power Isolation |
|
Power Supply |
Nominal:24VDC, Range: 19.2~28.8VDC |
|
Field Power Current |
Max. DC 8A |
|
IO Modules Supported |
32 pcs |
|
Wiring |
Max.: AWG 18 |
|
Installation |
35mm DIN-Rail |
|
Size |
115*51.5*75mm |
|
Weight |
130g |
|
Environment Specification |
|
|
Operating Temperature |
-35℃~60℃ |
|
Operating Temperature |
-35℃~70℃ |
|
Relative Humidity |
5~ 95%RH (No Condensation) |
|
Storage Temperature |
-40℃~85℃ |
|
Storage Humidity |
5~ 95%RH (No Condensation) |
|
Manufacturing Test |
-40℃~75℃ |
|
Ingress Protection Rating |
IP20 |
|
Modbus-RTU Parameter |
|
|
Protocol |
Modbus-RTU/ASCII |
|
Function Code |
01 / 02 / 03 / 04 / 05 / 06 / 15 / 16 / 23 |
|
Baud Rate |
2400~115200bps |
|
Station No. |
1~63(Dial-code switch configuration),64~247(Software |
|
Interface |
5 Pin screw terminal |
|
Data Bits |
78 |
|
Parity Checking |
N/A, Even, ODD |
|
Stop Bit |
1 ,2 |
|
Max. Bus Length |
1200m(RS485 ,2400 baud rate) |
|
Terminal resistance and |
DIP switch configuration |
A:Maximum total I/O is 8192 bytes, suitable for medium-sized fieldbus applications.
A:Maximum total I/O is 8192 bytes, suitable for medium-sized fieldbus applications.
Ideal for industries requiring high-speed, cost-effective distributed I/O:

- Digital Output Io
- Ethernet Ethernet Ip/Modbus
- Io Modbus
- modbus analog output module
- Modbus Control
- Modbus Converters
- modbus input module
- Modbus-TCP Io
- MRP Redundancy
- Multi Gigabit Switch
- Rtd Modbus Tcp
- Rtd Pt100 Io
- S7 Conveter
- S7-1200 Ethercat
- Schneider PLC communicate
- Serial Gateway
- Source Io 16 Digital Input

Automotive Industry