ODOT IP-PN-8IA IO-Link Series PROFINET Slave 8-Channel IO-Link Master Module
-
Min. Cycle TimeIP67 Protection Level
-
Expansion8 IO-Link Ports
-
OPERATING TEMP16 Configurable DI/DO
-
REDUNDANCYPROFINETSlave
PRODUCT DESCRIPTION
The IP-PN-8IA integrates PROFINET industrial Ethernet communication and IO-Link master functionality into a compact and robust distributed I/O solution. The module supports PROFINET RT real-time communication with a minimum communication cycle of 1ms, ensuring stable and deterministic data transmission between PLCs and field devices.
Supporting the IO-Link V1.1.4 standard, the module provides 8 Class A IO-Link ports. Each port independently supports configurable Pin 2 and Pin 4 digital input/output functions, allowing up to 16 digital I/O channels to be flexibly configured according to application requirements.
Designed for industrial environments, the IP-PN-8IA features an IP67-rated housing, integrated diagnostic functions, built-in temperature monitoring, automatic protection mechanisms, and online firmware upgrades without disassembly.
Benefits for Industrial Automation
-
1.Simplify Industrial Networking
Combines PROFINET communication and IO-Link master functionality in a single compact module, reducing wiring complexity and installation effort.
-
2. Improve System Flexibility
Supports configurable digital input/output channels, enabling flexible adaptation to different industrial applications.
-
3. Enhance System Reliability
Advanced diagnostic functions and intelligent temperature protection help minimize unexpected downtime and improve operational stability.
-
4.Reduce Maintenance Costs
By utilizing a non-potting process, the product's comprehensive maintenance costs are reduced by over 90%.
Technical Specifications
|
Power Port |
|
|
Us Power Supply Rated |
24VDC |
|
Us Power Supply Current |
Max.8A |
|
Ua Power Supply Rated |
24VDC |
|
Ua Power Supply Current |
Max.8A |
|
Us/Ua Power Interface |
2 M12: L-code 5 Pins, 1 pin end (input) and 1 hole end (output) |
|
Pin Definition |
M12 pin end (input) / hole end (output): |
|
Module Consumption |
Max.200mA@24VDC |
|
Network Port |
|
|
Number of Network |
2 M12, D-code 4 Pin, hole end, 1 IN, 1 OUT |
|
Pin Definition |
Pin1: Sender Tx+ |
|
IO-Link Class-A Port |
|
|
Quantity |
8 M12, A-code 5 Pin, hole end |
|
Port Definition |
Pin1: 24VDC (Us+), positive power supply |
|
Output Power Supply |
(1) Pin1(Us+)/Pin3(Us-): Rated output current 1.6A |
|
Communication Protocol |
|
|
Protocol |
PROFINET IO Device |
|
Fieldbus Bytes |
Input: Max.1440 Bytes |
|
RT |
Support, the minimum period of RT communication is 1ms. |
|
IRT |
Not supported |
|
MRP |
Not supported |
|
MRPD |
Not supported |
|
IO-Link Communication Protocol |
|
|
Protocol Standard |
IO-Link V1.1 master protocol |
|
Process Data |
Each port input: Max.32 Bytes |
|
Transfer Rate |
COM1(4.8kbps), COM2(38.4kbps), COM3(230.4kbps), |
|
IO-Link Maximum Line |
Point-to-point 20 meters |
|
Dimension |
|
|
Dimension |
214 mm *60 mm *35.5 mm |
A: Yes. The module supports PROFINET RT real-time communication with a minimum communication cycle of 1ms.
A: No. The module does not support MRP media redundancy or ring network redundancy.
A: The module provides 8 Class A IO-Link master ports and can connect up to 8 IO-Link devices.
The IP-PN-8IA is widely used in industrial automation applications requiring reliable PROFINET and IO-Link communication, including

Automotive manufacturing systems

Packaging and assembly machinery

Smart factory automation

Material handling systems

Logistics and warehousing automation

Industrial sensor and actuator integration

Food and beverage production lines

Distributed industrial I/O systems


Automotive Industry