Tel: +86-0816-2538289
contact us
ODOT CN-8011 Modbus-RTU Network Adapter
Product Model:ODOT CN-8011
Product Feature:

CN-8011 Modbus-RTU Network Adapter
 Module Overview
CN-8011 Modbus-RTU network adapter supports standard Modbus-RTU communication, it supports function code of 01/02/03/04/05/06/15/16/23, and this device could monitor the IO module communication state in real time.

Please watch our latest Remote IO video at youtube:

https://www.youtube.com/watch?v=O86lTEV8UdM&pp=sAQA

  • Product Details
  • Technical Parameters
  • Applications
  • Product Details

    Product Characteristic

    CN-8011 Modbus-RTU Network Adapter
     Module Overview
    CN-8011 Modbus-RTU network adapter supports standard Modbus-RTU communication, it supports function code of 01/02/03/04/05/06/15/16/23, and this device could monitor the IO module communication state in real time.

    Please watch our latest Remote IO video at youtube:

    https://www.youtube.com/watch?v=O86lTEV8UdM&pp=sAQA

  • Technical Parameters

    Technical Parameter

    Adapter Hardware Parameter
    System Power Nominal Reverse Protection: YES :24Vdc, Range: 9-36Vdc
    Power Consumption:30mA@24Vdc
    Internal Bus Supply
    Current Max: 2.5A@5VDC
    Isolation:System Power to Field Power Isolation
    Power Supply Nominal: 24Vdc, Range:22-28Vdc
    Field Power Current:Max. DC 8A
    IO Modules Supported:32 pcs
    Wiring:Max.1.5mm²(AWG 16)
    Mounting Type:35mm DIN-Rail
    Size:115*51.5*75mm
    Weight:130g

    Environment Specification
    Operation Temperature -40~85℃
    Operation Humidity 5%-95% (No Condensation)
    Protection: IP20

    Modbus-RTU Parameter
    Protocol: Modbus-RTU/ASCII
    Function Code: 01 / 02 / 03 / 04 / 05 / 06 / 15 / 16
    Baud Rate: 2400~115200bps
    Station No. : 1~63(Dial-code switch configuration),64~247(Software configuration)
    Interface: 5 Pin screw terminal
    Data Bits: 7, 8
    Parity Checking: None, Even, ODD
    Stop Bit: 1, 2
    Max. bus length: 1200m( RS485, 2400 baud rate)
    Terminal resistance and offset resistance: Dial-code switch configuration