Product Details
Technical parameters
General ParametersPowerMax.140mA@5.0VdcIsolationI/O to internal bus: opto-couple isolation (3KVrms)Field PowerNominal:24Vdc, Range:22-28VdcVCLAMP VoltageNominal:24Vdc, Input range:12-36VdcWiringI/O wiring: Max.1.5mm²(AWG 16)Mounting Type35mm DIN-RailSize115*14*75mmWeight65gEnvironment SpecificationOperational Temperature-40~85℃Operational Humidity5%-95% (No Condensation)Protection ClassIP20Output ParametersChannel Number16 channel sink type outputLED Indicator16 channel output LED indicatorRated Currentsingle channel output: Max.1000mA simultaneously output: Max.500mALeakage CurrentMax. 10uAOn ResistanceTypical value: 500mΩ
http:// www.odotautomation.com 134 / 279 TEL: +86-0816-2538289
Output DelayOFF to ON: Max.100us ON to OFF: Max.150usProtection FunctionOver-temperature shut down: typical value 160℃ Overcurrent protection: typical value 1.8A Short circuit protection: supported
Product Characteristic
CT-221F 16 channels digital output/24VDC/Sink type/output is 0V, the output low level is validModule features◆ the module supports 16 channels digital output, the output voltage is 0V andthe output low level is valid.◆ the module can drive field equipment (relay, solenoid valve, etc.)◆ the internal bus and field output of the module both adopt electromagneticisolation◆ the module carries 16 digital output channel LED indicator◆ the module has the function of thermal shutdown and over current protection
Technical Parameters
Technical Parameters