1. Module Type
2. State indicator
3. N/A
4. Wiring Terminal and identification
5. Internal Bus
6. Field Power
7. Buckle
8. Grounding Resilient Sheet
9. Fixed Wiring Harness
General parameters
Power: Max.50mA@5.0Vdc
Isolation: I/O to internal bus: magnetic isolation (2.5KVrms)
Field Power: Not used
Wiring: I/O Wiring: Max.1.5mm²(AWG 16)
Mounting Type: 35mmDIN-Rail
Size: 115*14*75mm
Weight: 65g
Environment Specification
Operational Temperature: -40~85℃
Operational Humidity: 5%~95% RH(No Condensation)
Protection Class: IP20
Input Parameter
Channel Number: 4 Channels
LED Indicator: 4 Input LED Indicators
Sensor Type: J / K/ E / T / S / R / B / N type thermocouples
Acquisition Accuracy:
±0.3% Full Scale, @25℃
±0.5% Full Scale, @-40~85℃
Single Channel Sampling Rate: 50Hz (Max.)
Measuring Range ℃
J Type -210~1200℃
K Type -270~1370℃
E Type -270~1000℃
T Type -270~400℃
S Type -50~1760℃
R Type -50~1760℃
B Type 0~1820℃
N Type -270~1300℃
Data Format 16-Bit Signed Integer (Integer)