CT-5321: Modbus Serial Port Module factory and manufacturers | ODOT

CT-5321: Modbus Serial Port Module

Product Feature:

CT-5321 Modbus Serial Port Module

1 Module Description

The Modbus serial port module supports 1 channel RS485/RS232 /RS422(optional), supports Modbus RTU/ASCII protocol, and supports master, slave and free transparent transmission mode.

The serial Module CT-5321 could be applied with the adapter modules, so it could convert Modbus into other protocols such as Modbus TCP, Profinet, EtherCAT, EtherNet/IP, etc. When the module is used, serial port parameters and Modbus instructions should be configured in IO Config software.

Devices with RS485/RS232/RS422 interface, which support modbus-RTU/ASCII, could be applied with CT-5321 to realize interconnection with upper PLC or upper computers. CT-5321 could be applied with devices such as: PLC, DCS, remote IO, VFD, motor start protection device, intelligent high and low voltage electrical apparatus, power measurement device, intelligent field measurement equipment and instruments, etc.


Product Detail

Demo Video

Product Tags

Product Download

Product Details

CT-5321 Modbus Serial Port Module

Technical Parameters

General parameters

Power Max.500mA@5.0Vdc
Isolation I/O to internal bus: opto-couple isolation (3KVrms)
Field Power Nominal:24Vdc, Range:20-28Vdc
Wiring I/O Wiring: Max.1.5mm²(AWG 16)
Mounting Type 35mmDIN-Rail
Size 115*14*75mm
Weight 65g

Environment Specification

Operational
Temperature
-40~85℃
Operational
Humidity
5%~95% RH(No Condensation)
Protection Class IP20

Serial Port Parameters

Note: M represents the valid parameters of master mode, S represents the valid parameters of slave mode, and F represents the valid parameters of free transparent transmission mode

M/S/F:Channel
Number
1Channel
M/S/F:Interface RS485/RS232/RS422
M/S:Protocol Modbus RTU/ASCII
M/S/F:Working
Mode
Modbus Master, Slave, Transparent Transmission
M/S/F:Baud Rate 300bps-500Kbps
M/S/F:Data Bit Bit 7, Bit 8
M/S/F:Parity
Checking
None, Odd, Even
M/S/F:Stop Bit Bit1, Bit2
M/S/F:
Character Interval
1.5t-200t
F: Byte Order
Conversion
Prohibit, Enable
M/F:Response
Timeout
Customized, default: 1000
M/F: Polling
Timeout
Customized, default: 100
M: Read Data
Processing Mode
Hold the last input value, clear the input value
M: Data
Output Mode
Polling, event triggering (data changes)
M: Module
Control Enable
Prohibit, Enable
M: Module
Control Mode
Level trigger (continuously valid), rising edge trigger (single
valid)
M: Power on
Event Output
Prohibit, Enable
S:Slave ID Customized, default: 1
S:Response
Time
Customized, default: 50